Product Features
Medical & ITE safety meet |
2 MOPP input to output isolation |
DOE Efficiercy Level VI & CoC V5 Tier2(2016) |
Low Leakage current≤100μA |
≤0.075W standby power |
Up to 5000m operating altitude |
Input |
Input Voltage:80-264VAC
Frequency Range:47-63Hz
Input Current:0.8A,at 80VAC
Touch Leakage Current:≤ 100μA at 264VAC
Environmental
Operationg Temperature: 0~45℃
Storage Temperature:- 20~60℃
Operating Humidity:10 to 90% RH,non-condensing
Storage Humidity::5 to 90% RH
Operating Altitude:5,000 M
General
Dimensions:88.5(L)×30.5(W)×48.8(H)mm
Weight:128g
MTBF:>100000hrs MIL-HKBK-217 AI 25℃
Isolation:5,656VDC Input to Output
Safety Approvals | ||||||||||||
Safety Agency/Mark | Medical | ITE | ||||||||||
CB | IEC60601-1 | - | ||||||||||
TuV Rheinland/Mark | | | | EN60601-1 | | | | - | | | | |
UL | | | | ANSI/AAMI ES 60601-1 | | | | - | | | | |
| | | | CAN/CSAC22.2NO.60601-1 |
Models & Ratings
Model Number | Voltage | Current | Rated Power | Ripple & Noise | Voltage Tolerance | Line & Load | Efficiency | Start Up Delay |
(V) | (A) | (max) | Regulation | |||||
UES24LZ1-120200SPA | 12.0 | 0.01-2.0 | 24W | 150mVpk-pk | ±5% | Line: ±1% Load: ±5% | 86.8% | ≤3s |